Plan Review Notes
Plan Review Notes For Permit 20030797
Permit Number 20030797
Review Stop B
Sequence Number 2
Notes
Date Text
2020-03-19 08:58:43RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ROOFING UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL511288-R17 SUBMITTED:
 CLEARLY MARK WHICH MAXIMUM DESIGN PRESSURES ASSEMBLY
 FROM SEC. 5.6.3 OF PRODUCT APPROVAL IS GOING TO BE
 USED. OR IF USING THE FRSA/TRI APRIL 2012 (04-12)
 REVISED EDITION, THEN PROVIDE COMPLETE INFORRMATION
 SHOWING THE DETERMINATION OF DESIGN WIND LOADS AND
 UNDERLAYMENT FASTENING AS REQUIRED BY SEC. 5.6.3 OF
 PRODUCT APPROVAL SUBMITTED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 SELECTED SYSTEM #10 ON PAGE 7 OF 10 OF FLORIDA PRODUCT
 APPROVAL SUBMITTED HAS A MAXIMUM DESIGN PRESSURE OF
 -67.5 PSF. ACCORDING TO SEC. 5.6.3.2 ON PAGE 7 OF 10 OF
 PRODUCT APPROVAL SUBMITTED THIS ASSEMBLY CAN NOT BE
 USED. FOR MECHANICALLY ATTACHED BASED SHEET THE MAXIMUM
 DESIGN PRESSURE FOR THE SELECTED ASSEMBLY SHALL MEET OR
 EXCEED THAT REQUIRED UNDER FRSA/TRI APPENDIX A, TABLE
 1A. SELECTED ASSEMBLY DOESN'T MEET THAT DESIGN
 PRESSURE. PLEASE SELECT ANOTHER ASSEMBLY OR
 ALTERNATIVELY, PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED ON SEC. 5.6.3.2 OF PRODUCT
 PROPOSAL SUBMITTED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]