2020-04-10 08:51:17A NEW GAS PLAN HAS BEEN SUBMITTED FOR REVIEW.
 1) ) SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 2) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-FUEL GAS SEC.410.2 (7).
 3) SEDIMENT TRAPS ARE REQUIRED AT THE POOL HEATERS PER
 2017 FBC-GAS SEC. 408.4.
  
  