2020-04-01 07:46:21 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20030695 |
| |
| CODES IN EFFECT: |
| |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE ENERGY GAUGE FORM R405 IS MISSING FROM THE |
| ENERGY COMPLIANCE SUBMITTAL- SECTION R405.2 FBC EC. |
| |
| 2) PROVIDE THE MANUAL J WORKSHEETS WITH THE AC SYSTEM |
| SIZING CALCULATIONS- SECTION R403.7.1 FBC EC. |
| |
| 3) PLEASE SHOW A DETAIL OF HOW YOU ARE GOING TO ANCHOR |
| THE A/C UNIT OUTSIDE. FBC RES M1307.2 ANCHORAGE OF |
| APPLIANCES. |
| |
| 4) THE CONTRACTOR MUST SIGN AND DATE THE DRAWINGS |
| PROVIDED. FBC WPB- 107.3.4.2 CERTIFICATIONS BY |
| CONTRACTORS |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |