2020-03-20 10:07:02 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT- 20030695 |
| |
| CODES IN EFFECT: |
| |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| SHEET 7 OF 14: LEVEL 2- PLEASE SHOW THE LOCATION OF THE |
| MAIN RETURN GRILL, INCLUDE SIZE AND CFM?S. |
| SHEET 7 OF 14: LEVEL 2- RETURN AIR OPENINGS MUST MEET |
| FBC RES M1602.2 (4) RETURN AIR SHALL NOT BE TAKEN FROM |
| A CLOSET, BATHROOM, TOILET ROOM, KITCHEN, GARAGE, |
| MECHANICAL ROOM, BOILER ROOM, FURNACE ROOM OR |
| UNCONDITIONED ATTIC. |
| SHEET 13 OF 14: LEVEL 1- PLEASE SHOW RETURN CFM IN THE |
| CONDITIONED AREA. ALSO SHOW THE SUPPLY AND RETURN |
| DUCTWORK WITH SIZES. SHEET 14 OF 14: PLEASE SHOW BOTH |
| SUPPLY AND RETURN REGISTERS AND CFM?S FOR EACH. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |