Plan Review Notes
Plan Review Notes For Permit 20030695
Permit Number 20030695
Review Stop M
Sequence Number 1
Notes
Date Text
2020-03-20 10:07:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20030695
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 SHEET 7 OF 14: LEVEL 2- PLEASE SHOW THE LOCATION OF THE
 MAIN RETURN GRILL, INCLUDE SIZE AND CFM?S.
 SHEET 7 OF 14: LEVEL 2- RETURN AIR OPENINGS MUST MEET
 FBC RES M1602.2 (4) RETURN AIR SHALL NOT BE TAKEN FROM
 A CLOSET, BATHROOM, TOILET ROOM, KITCHEN, GARAGE,
 MECHANICAL ROOM, BOILER ROOM, FURNACE ROOM OR
 UNCONDITIONED ATTIC.
 SHEET 13 OF 14: LEVEL 1- PLEASE SHOW RETURN CFM IN THE
 CONDITIONED AREA. ALSO SHOW THE SUPPLY AND RETURN
 DUCTWORK WITH SIZES. SHEET 14 OF 14: PLEASE SHOW BOTH
 SUPPLY AND RETURN REGISTERS AND CFM?S FOR EACH.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  