Date |
Text |
2020-03-27 11:55:44 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A-1, MP-1- TUB BOX INFILL: PROVIDE A UL TESTED |
| AND APPROVED FIRESTOPPING ASSEMBLY FOR THE DRAIN PIPE |
| PENTRATION THROUGH THE FIRE-RATED FLOOR/CEILING |
| ASSEMBLY- SECTION 714.4.1 FBC B. THE PIPE SHALL ALSO BE |
| PROTECTED FROM CORROSION BY SHEATHING OR WRAPPING IN |
| ACCORDANCE WITH SECTION 305.1 FBC P. |
| |
| 2) MP-1: PLEASE UPDATE THE CODE COMPLIANCE DATA TO |
| INDICATE THE FLORIDA PLUMBING CODE SIXTH EDITION 2017, |
| AND REMOVE THE FBC RES P2709.1 REFERENCE FROM THE |
| SHOWER DETAIL. THIS PROJECT IS NOT GOVERNED BY THE |
| SINGLE-FAMILY RESIDENTIAL CODE BECAUSE IT A MULTI-STORY |
| R-2 OCCUPANCY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |