2020-03-31 15:23:04 | SHELL ALTERATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE PROVIDE THE EXTERIOR LIGHT GAGE WALL FRAMING |
| DETAILS. |
| 2) PLEASE PROVIDE THE EXTERIOR WALL CLADDING DETAILS OR |
| PRODUCT APPROVALS. |
| 3) PLEASE PROVIDE THE COLUMN INTUMESCENT PAINT DETAILS |
| (FBC 704.13.1) FOR A 2 HOUR FIRE RATING OF THE COLUMNS |
| PER FBC TABLE 601 |
| 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS. ALL PRODUCT APPROVALS NEED TO BE |
| REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| OF RECORD. |
| |
| 553.79(5) 2016, THIS IS A THRESHOLD BUILDING. THE |
| FOLLOWING IS REQUIRED PRIOR TO COMMENCEMENT: |
| |
| 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT |
| OF UNDERSTANDING; |
| |
| 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL |
| PROPOSED INSPECTORS. |
| |
| 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT |
| REQUIRED BY FS553.79(7)(D). |
| |
| (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS |
| AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| THIS CHAPTER 553 AND CHAPTER 633. |
| |
| 4. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A). |