2020-10-06 14:42:35FAILED
  
 THIS IS A SIGN TYPE 1A - FASCIA IDENTITY SIGN
  
 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT REVERSE CHANNEL LETTERS ARE FABRICATED OUT OF
 ALUMINUM WITH A MINIMUM METAL THICKNESS OF .060 INCHES.
 THE THICKNESS IS NOT PROVIDED.
  
 2) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE
 STUD MOUNTS TO BE SERIES 316 STAINLESS STEEL ANCHOR
 BOLTS. PROVIDE VERIFICATION THAT THE STAINLESS STEEL
 STUDS SHOWN ON THE PLANS COMPLY WITH THIS
  
 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRES
 THAT ALL CONDUIT, CROSSOVERS, WIRING NECESSARY FOR THE
 SIGN?S ELECTRICAL CONNECTION TO BE CONCEALED AND NOT
 VISIBLE TO THE PUBLIC. THE WIRES FROM THE WALL TO THE
 SIGN ARE EXPOSED.
  
 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT THE CHANNEL DEPTH CAN BE NO MORE THAN FOUR (4)
 INCHES. THE DEPTH WAS NOT PROVIDED ON THE PLANS.
  
 PERMITTED: 53 SF
 PROPOSED: 10.99 SF
  