Plan Review Notes For Permit 20030581 |
Permit Number |
20030581 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-07-12 16:08:33 | BUILDING PROVISO: | | SHEET A-103. THE CONDENSING UNIT STAND IS TO CARRY AN | | NOA OR HAVE A | | STTRUCTURAL WIND LOADING ANALYSIS COMPLETE WITH | | ATTACHMENT DETAILS. THE | | UNIT TO STAND AND STAND TO ROOF ATTACHMENT SHALL BE PER | | THE NOA OR STRUCTURAL | | ENGINEERING CALCULATION/ INSTRUCTIONS. THE NOA OR | | STRUCTURAL CALCULATIONS | | MUST BE PROVIDED TO THE ENGINEER OF RECORD FOR APPROVAL | | AND TOTHE BUILDING | | DEPARTMENT FOR APPROVAL PRIOR TO CALLING FOR THE FIRST | | INSPECTION. | | BUILD. REVIEW J. WITMER | | |
|