2020-06-12 13:00:55 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20030581 |
| ADD: 301 N. OLIVE AVE. 4TH FLOOR |
| CONT: ROBLING ARCHITECTURE CONSTRUCTION |
| TEL: 561-649-6705 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUESDAY MAY 5TH/ 2020 |
| ACTION: DENIED |
| |
| 1) SHEET A-103 NOTE # 6 INDICATES A NEW ROOF TOP |
| CONDENSING UNIT SEE MECHANICAL SHEETS. SHEET M-6NOTE # |
| 1 STATES THE NEW CONDENSING UNIT SHALL BE 180 MPH WIND |
| RATED. SHEET M-7 NOTE # 3 STATES THAT THE UNIT |
| ATTACHMENT TO CONCRETE PAD PER THE MANUFACTURERS |
| SPECIFICATIONS, STAND SHALL HAVE A MIAMI-DADE NOA. |
| SHEET M-7 NOTE # 4 STATES ENGINEERED TIE-DOWN |
| INSTALLATION REQUIRED. |
| |
| 1A) THE PLANS DO NOT INDICATE HOW THE CONDENSING UNIT |
| WILL BE ANCHORED TO THE CONDENSING STAND. FOR ALL ROOF |
| TOP EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| |
| 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 1B) THE SHEET M-6 STATES THE WIND SPEED IS TO BE |
| DESIGNED TO 180 MPH (VULT). 2017 FBC-B 1603.1.4 WIND |
| DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND |
| LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS |
| GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM |
| OF THE STRUCTURE: |
| 1B)(1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND |
| GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| 1B)(2.) RISK CATEGORY. |
| 1B)(3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF |
| MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE |
| 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| 1B)(4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 1B)(5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| 1)(6) TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE BUILDING |
| FOR NEGATIVE PRESSURES. IS THERE A 3 FOOT PARAPET OR |
| HIGHER ALL AROUND THE BUILDING? 1609.3.1 WIND SPEED |
| CONVERSION VULT TO VASD. |
| 2) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION. |
| 2017 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2) QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| FOR ADDITIONAL INFORMATION PLEASE CALL KEN CONRAD CHIEF |
| BUILDING INSPECTOR AT 561-805-6666. |
| |
| 3) COMPONENTS & CLADDING. 2017 FBC-B 1609.6.4.4.1 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(G) PRE-ENGINEERED A/C STANDS |
| |
| 4A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 5) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| |
| 6) 2017 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS |
| OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING |
| ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED |
| STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL |
| WILL HAVE TO CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE |
| GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN |
| INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. |
| SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER |
| OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) IN HEIGHT |
| OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS |
| VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE |
| LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET |
| WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE |
| PARAPET WALL. |
| |
| 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |