2020-03-16 17:23:43 | RESIDENTIAL (R3) SUBMITTAL BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- BUILDING REVIEW WAS ORIGINALLY APPROVED ON |
| 06/06/2019 WITH A PROVISO. THE PROVISO WAS TO ALLOW |
| CONTRACTOR TO OBTAIN THE PERMIT.AND TO SUBMIT THE |
| REQUIRED INFORMATION PRIOR TO INSPECTIONS. AS OF TODAY |
| THE INFORMATION REQUESTED ON THE PROVISO HAS NOT BEEN |
| SUBMITTED. PLEASE PROVIDE ALL THE INFORMATION REQUESTED |
| ON THE PROVISO. SEE COPY OF PROVISO BELOW: |
| |
| BUILDING REVIEW APPROVED WITH PROVISO: |
| 1- SPECIFY ALL STRUCTURAL CONNECTORS FOR ALL INFILL |
| EXTERIOR WALLS IN NEW KITCHEN. |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| A) SINGLE HUNG WINDOW SIZE (5'-2"WIDTH X 4'-6" HEIGHT ) |
| SPECIFIED ON THE WINDOW SCHEDULE FOR WINDOW W-112. |
| B) WINDOW MULLIONS (IF USED) PLANS ARE NOT CLEAR. AND, |
| CLEARLY SPECIF MULLION SIZE TO VERIFY COMPLIANCE WITH |
| THE CALCULATED DESIGN PRESSURES. |
| C) FRONT DOOR PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. |
| NEED TO PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL (2 |
| COPIES), INCLUDING THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED. THE |
| FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS |
| IF PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT. |
| 3- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |
| 10/20/2020 TALKED TO SAMANTHA HILL REVISED COMMENTS. |
| REMOVED INSPECTIONS PRIVATE PROVIDER COMMENT #1. |
| INSPECTIONS BY PRIVATE PROVIDER ARE HANDLED BY RICHARD |
| GATHRIGHT. JG. |