Plan Review Notes
Plan Review Notes For Permit 20030509
Permit Number 20030509
Review Stop B
Sequence Number 1
Notes
Date Text
2020-03-18 15:42:22OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) SHOW DOOR MARKED 317 TO COMPLY WITH FBC 1005.7
 ENCROACHMENTS INTO THE REQUIRED MEANS OF EGRESS WIDTH.
 2) SHOW GLASS WALLS AND DOORS TO BE SAFETY GLAZING PER
 FBC 2406
 3) PLEASE PROVIDE AN EXISTING FLOOR PLAN TO SHOW THE
 EXISTING USE OF THE SPACE. MAY AFFECT EGRESS
 REQUIREMENTS FOR THE BUILDING - FBC EXISTING 1012.4.1