Plan Review Notes For Permit 20030440
Permit Number 20030440
Review Stop P
Sequence Number 2
Notes
Date Text
2020-04-09 14:06:03REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20030440 2380 PALM BEACH LAKES BLVD
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. REGARDING RESPONSES FOR REVIEW COMMENTS 1 AND 2, NEW
 PLAN SHEETS P2 AND P3 HAVE NOT BEEN UPLOADED.
 2. REGARDING COMMENT 3, THE TRENCH DETAIL SHOWS CRUSHED
 ROCK AROUND THE PIPE. PER FBC PL 306.3 LOOSE EARTH FREE
 FROM ROCKS, BROKEN CONCRETE AND FROZEN CHUNKS SHALL BE
 PLACED IN THE TRENCH IN 6-INCH (152 MM) LAYERS AND
 TAMPED IN PLACE UNTIL THE CROWN OF THE PIPE IS COVERED
 BY 12 INCHES OF TAMPED EARTH. PLEASE CORRECT.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  