2020-05-08 09:46:43 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 2) |
| |
| 3) |
| |
| 4) |
| |
| 5) SEVERAL OF THE REMODELED AREAS AND THE NEWLY |
| ENCLOSED AREAS DO NOT COMPLY WITH THE WALL SPACING |
| REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL |
| BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY |
| ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 |
| FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC |
| 210.52; FBC RE E3901.2.1 PROPOSED GREAT ROOM AND BAR |
| ARE |
| |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |