Plan Review Notes
Plan Review Notes For Permit 20030355
Permit Number 20030355
Review Stop B
Sequence Number 2
Notes
Date Text
2020-05-08 15:54:29PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 1. FBC B 107.2.1, THE ARCHITECTUAL DRAWINGS DO NOT HAVE
 THE DESIGNER'S NAME AND SIGNATURE.
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES &
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 2. FBC B 107.2.1 INDICATE WHERE THE WINDOW WALL SYSTEM
 ( NOA NO.19-0326.07 ) WILL BE INSTALLED.
  
 3. FBC B 107.2.1 PLEASE CLARIFY IF THE STEEL PLATE
 CONNECTION DETAIL 13/S2 REQUIRES FASTENER SPACING OF
 12" OR 16" O.C.
  
 4. FBC B 107.2.1 PLEASE CLARIFY THE WELD SIZES ON PAGES
 S-2 AND S-3.1 AS THE DETAILS CALL FOR ALL AROUND FILLET
 WELDS, 1" WELD SIZE/THICKNESS. THAT WELD SIZE IS
 THICKER THAN THE BASE MATERIALS.
  
 IN ADDITION TO CORRECTING THE WELD SIZE ON THE PLANS,
 AT TIME OF INSPECTION PLEASE PROVIDE THE FOLLOWING:
 AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
 AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.
  