2020-03-17 14:07:19 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT- 20030355 |
| |
| CODES IN EFFECT: |
| |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) IDENTIFY AHU?S ON DRAWINGS. |
| |
| 2) PLEASE PROVIDE A DETAIL DRAWING OF THE RETURN DUCT |
| IN HALL THAT BEDROOM 2 AND 3 ARE DUCTED TO, THE A |
| SHEETS SHOW THIS AREA IS A CLOSET. RETURN AIR CANNOT |
| COME FROM A CLOSET OR THE MASTER BATH UPSTAIRS. |
| (. SEE FBCEC 103.2 INFORMATION ON CONSTRUCTION |
| DOCUMENTS.)(SEE FBC RES M1602.2 (4) RETURN AIR SHALL |
| NOT BE TAKEN FROM A CLOSET, BATHROOM, TOILET ROOM, |
| KITCHEN, GARAGE, MECHANICAL ROOM, BOILER ROOM, FURNACE |
| ROOM OR UNCONDITIONED ATTIC. |
| |
| 3) AHU?S IN ATTIC MUST MEET SECTION FBC RES M1305.1.3 |
| APPLIANCES IN ATTIC. SEE ALSO FBC EC R403.3.6 |
| |
| 4) DUCTWORK IN THE GARAGE MUST MEET FBC RES R302.5.2 |
| |
| 5) PROVIDE SPEC SHEETS FOR THE HOOD AND THE RANGE, ALSO |
| PROVIDE FUEL SOURCE FOR THE NEW RANGE. |
| (. SEE FBCEC 103.2 INFORMATION ON CONSTRUCTION |
| DOCUMENTS.) |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |