Plan Review Notes
Plan Review Notes For Permit 20030355
Permit Number 20030355
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-08 06:59:551) SHOW THE LOCATION OF THE GAS WATER HEATERS ON THE
 PLAN. IF THE WATER HEATERS ARE TANKLESS, THEY SHALL BE
 INSTALLED PER THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS WHICH USUALLY REQUIRE 4 FEET FROM ANY
 OPERABLE DORRS, WINDOWS OR BUILDING OPENINGS.
 2) SHOW THE LOCATION OF THE FIREPLACE ON THE FLOOR
 PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 3) REVISE THE BTU LOAD TO READ 633,000 BTU'S.
 4) THE 1 INCH CSST TO THE FIREPLACE APPEARS TO BE
 UNDERSIZED PER THE REFERENCED SIZING TABLE. INDICATE
 THE EHD OF THE CSST OFR THIS LINE.
 5) SUBMIT THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING SHOWN ON THE GAS
 RISER.
 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 FIREPLACE, DRYER, AND RANGE.PER THE 2017 FBC-FUEL GAS
 CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017 FBC-RES.
 SEC. G 2407.1 AND G2439.4 (CLOTHES DRYERS).
 7) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 8) THE EXTERIOR GRILL SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION REQUIREMENTS. A
 HOOD MAY BE REQUIRED ABOVE THE GRILL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  