2020-05-08 06:59:55 | 1) SHOW THE LOCATION OF THE GAS WATER HEATERS ON THE |
| PLAN. IF THE WATER HEATERS ARE TANKLESS, THEY SHALL BE |
| INSTALLED PER THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS WHICH USUALLY REQUIRE 4 FEET FROM ANY |
| OPERABLE DORRS, WINDOWS OR BUILDING OPENINGS. |
| 2) SHOW THE LOCATION OF THE FIREPLACE ON THE FLOOR |
| PLAN. WPB AMEND. TO FBC SEC. 107.2.1. |
| 3) REVISE THE BTU LOAD TO READ 633,000 BTU'S. |
| 4) THE 1 INCH CSST TO THE FIREPLACE APPEARS TO BE |
| UNDERSIZED PER THE REFERENCED SIZING TABLE. INDICATE |
| THE EHD OF THE CSST OFR THIS LINE. |
| 5) SUBMIT THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING SHOWN ON THE GAS |
| RISER. |
| 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| FIREPLACE, DRYER, AND RANGE.PER THE 2017 FBC-FUEL GAS |
| CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017 FBC-RES. |
| SEC. G 2407.1 AND G2439.4 (CLOTHES DRYERS). |
| 7) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| 8) THE EXTERIOR GRILL SHALL BE INSTALLED IN ACCORDANCE |
| WITH THE MANUFACTURER'S INSTALLATION REQUIREMENTS. A |
| HOOD MAY BE REQUIRED ABOVE THE GRILL. |
| |