2020-05-26 13:51:09 | REVIEW FBC-2017 MECHANICAL |
| PERMIT-20030302 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SHOW HOW THIS COMMERCIAL RANGE MODEL # |
| PRD486WDGU MEETS FBC M 917.2 FOR RESIDENTIAL USE. |
| |
| 2) PLEASE PROVIDE THE INSTALLATION INSTRUCTIONS AND |
| SPECS FOR BOTH THE RANGE AND THE HOOD THAT IS |
| RECOMMENDED BY THE MANUFACTURER OF THE RANGE. FBC FS |
| 107.2.1 |
| |
| 3) THE RANGE SHOWN ON THIS PROJECT ( PRD486WDGU ) |
| REQUIRES 103,000BTU OF GAS. PLEASE SHOW THE |
| MANUFACTURER RECOMMENDED HOOD ALONG WITH THE MAKEUP AIR |
| FOR THE CFM?S REQUIRED FOR THIS HOOD. FBC FS 107.2.1 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |