2020-03-13 10:55:40 | CODES IN EFFECT: |
| |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED |
| |
| ORIGINAL PERMIT # 19091103 SHOWED A 4 BEDROOM HOUSE. |
| THE ENERGY CALCULATIONS AND THE MECHANICAL SHEET |
| MATCHED. THIS REVISION #20030292 NOW SHOWS A 5 BEDROOM |
| HOUSE. THE ROOMS NOW DO NOT MATCH THE ENERGY |
| CALCULATIONS. THE DUCT SIZES DO NOT MATCH, THERE ISN?T |
| A WALKIN CLOSET BUT THE ENERGY CALCULATIONS CALLS OUT A |
| DUCT IN THE MASTER CLOSET. PLEASE PROVIDE AN ENERGY |
| CALCULATION THAT MATCHES THIS 5 BEDROOM HOUSE. |
| |
| CODE SECTION: FBC EC 107.2 CONSTRUCTION DOCUMENTS. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |