2020-03-13 10:55:40CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 ORIGINAL PERMIT # 19091103 SHOWED A 4 BEDROOM HOUSE.
 THE ENERGY CALCULATIONS AND THE MECHANICAL SHEET
 MATCHED. THIS REVISION #20030292 NOW SHOWS A 5 BEDROOM
 HOUSE. THE ROOMS NOW DO NOT MATCH THE ENERGY
 CALCULATIONS. THE DUCT SIZES DO NOT MATCH, THERE ISN?T
 A WALKIN CLOSET BUT THE ENERGY CALCULATIONS CALLS OUT A
 DUCT IN THE MASTER CLOSET. PLEASE PROVIDE AN ENERGY
 CALCULATION THAT MATCHES THIS 5 BEDROOM HOUSE.
  
 CODE SECTION: FBC EC 107.2 CONSTRUCTION DOCUMENTS.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  