Plan Review Notes
Plan Review Notes For Permit 20030291
Permit Number 20030291
Review Stop M
Sequence Number 1
Notes
Date Text
2020-03-17 15:00:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20030291
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) NEED TO REVISE THE ENERGY CALCULATIONS TO MATCH THE
 5 BEDROOM PLANS. FBC EC R101.5.1.1.2; FBC RES RE403.7
  
 2) NEED TO PROVIDE A MECHANICAL SHEET OF THE CORRECT 5
 BEDROOM PLAN. FBC FAC 107.1
  
 MECHANICAL PLAN MUST MATCH THE A SHEETS: A SHEETS AND
 PERMIT IS FOR A 5 BEDROOM HOUSE, THE MECHANICAL SHEET
 IS A 4 BEDROOM HOUSE AND SO ARE THE ENERGY
 CALCULATIONS.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  