Plan Review Notes
Plan Review Notes For Permit 20030278
Permit Number 20030278
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-07-17 15:13:45THE DOOR THAT WAS REMOVED IS A PART OF THE STAIRWELL
 PRESSURIZATION SYSTEM THAT WAS PREVIOUSLY TESTED, AND
 APPROVED. STAIRWELL PRESSURIZATION WILL HAVE TO BE
 RETESTED, AND G.C. WILL NEED TO COMMUNICATE WITH THE
 CONTRACTOR TO DETERMINE WHAT ADJUSTMENTS NEED TO BE
 MADE BEFORE TESTING WILL COMMENCE.
  
 S. THOMAS
 561-804-4728