2020-04-16 10:12:50 | STEPHNIE HALL FROM ELECTRASERVE EMAILED ME THE |
| INFORMATION PETER VALENTI ASKED FOR. THE OTHER ISSUES I |
| ASKED ABOUT ARE INCLUDED IN THE MASTER PERMIT. PROJECT |
| IS APPROVED. |
2020-04-14 10:34:52 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT-20030251 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THIS IS A NEW INSTALLATION FOR A NEW BUILDING. |
| PLEASE PROVIDE SPECS. FOR GENERATOR AND FUEL TANKS. |
| SHOW ALSO HOW THIS GENERATOR WILL BE ANCHORED. PLEASE |
| SHOW DETAILS OF GENERATOR SUPPORT SLAB. FBC FS 107.2.1 |
| 2) PROVIDE COMPLETE MECHANICAL DRAWINGS SHOWING A CODE |
| COMPLIANT INSTALLATION OF THIS GENERATOR INCLUDING |
| COMPLETE DIAGRAM OF FUEL PIPING INSTALLATION. FBC M |
| CHAPTER 13 FUEL OIL PIPING AND STORAGE. |
| 3) ALSO NEEDED ON THESE CODE COMPLIANT PLANS SHOW THE |
| GENERATOR LOCATION ALONG WITH LOT SETBACKS. SHOW THAT |
| THE EXHAUST TERMINATION OF THIS GENERATOR WILL COMPLY |
| WITH FBC M 501.3; FBC FS 107.2.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |