Plan Review Notes
Plan Review Notes For Permit 20030198
Permit Number 20030198
Review Stop P
Sequence Number 1
Notes
Date Text
2020-03-25 16:21:031ST REVIEW FBC-2017 PLUMBING
 PERMIT #20030198
 3/25/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 12: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW
 WATER HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 2) SHEET 12: REFER TO SECTIONS P2801.6, P2801.6.1,
 P27801.6.2 FBC RES: A PAN AND A PAN DRAIN ARE REQUIRED
 FOR THE WATER HEATER. THE PAN DRAIN SHALL BE A 3/4"
 PIPE WHICH SHALL EXTEND FULL SIZE AND TERMINATE OVER A
 SUITABLE LOCATED WASTE RECEPTOR, OR SHALL EXTEND TO THE
 EXTERIOR OF THE BUILDING AND TERMINATE NOT LESS THAN 6
 INCHES AND NOT MORE THAN 24 INCHES ABOVE THE GROUND
 SURFACE. PLEASE SEE TABLE 2906.5 FOR ALLOWABLE PIPE
 MATERIAL. PLEASE CORRECT THE PLAN TO SHOW COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  