2020-03-25 16:21:03 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT #20030198 |
| 3/25/20 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 12: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW |
| WATER HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS. |
| |
| 2) SHEET 12: REFER TO SECTIONS P2801.6, P2801.6.1, |
| P27801.6.2 FBC RES: A PAN AND A PAN DRAIN ARE REQUIRED |
| FOR THE WATER HEATER. THE PAN DRAIN SHALL BE A 3/4" |
| PIPE WHICH SHALL EXTEND FULL SIZE AND TERMINATE OVER A |
| SUITABLE LOCATED WASTE RECEPTOR, OR SHALL EXTEND TO THE |
| EXTERIOR OF THE BUILDING AND TERMINATE NOT LESS THAN 6 |
| INCHES AND NOT MORE THAN 24 INCHES ABOVE THE GROUND |
| SURFACE. PLEASE SEE TABLE 2906.5 FOR ALLOWABLE PIPE |
| MATERIAL. PLEASE CORRECT THE PLAN TO SHOW COMPLIANCE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |