2020-03-14 02:55:21COMBUSTION AIR IS REQUIRED FOR THE COOKTOP AND THE
 DRYER. PROVIDE VERIFICATION & CALCULATIONS HOW THE
 REQUIREMENTS ARE BEING MET.PROVIDE THE CODE SECTIONS
 FROM THE GAS CODE THAT YOU ARE USING IN THE DESIGN OF
 THE COMBUSTION AIR REQUIREMENTS. WPB AMEND. TO FBC SEC.
 107.2.1, FBC-FUEL GAS SEC.304.1.2ND REQUEST.
 NOTE: A NOTE HAS BEEN PLACED ON THE PLANS THAT READS
 "REQUIRES LOUVER DOOR OR VENT IN WALL." PLEASE READ THE
 PLAN REVIEW COMMENT AND REFER TO THE NOTED CODE
 SECTIONS. THE CODE REQUIRES CALCULATIONS, NOT A VAGUE
 NOTE THAT DOES NOT PROVIDE THE REQUIRED INFORMATION.
  