2020-03-14 02:55:21 | COMBUSTION AIR IS REQUIRED FOR THE COOKTOP AND THE | | DRYER. PROVIDE VERIFICATION & CALCULATIONS HOW THE | | REQUIREMENTS ARE BEING MET.PROVIDE THE CODE SECTIONS | | FROM THE GAS CODE THAT YOU ARE USING IN THE DESIGN OF | | THE COMBUSTION AIR REQUIREMENTS. WPB AMEND. TO FBC SEC. | | 107.2.1, FBC-FUEL GAS SEC.304.1.2ND REQUEST. | | NOTE: A NOTE HAS BEEN PLACED ON THE PLANS THAT READS | | "REQUIRES LOUVER DOOR OR VENT IN WALL." PLEASE READ THE | | PLAN REVIEW COMMENT AND REFER TO THE NOTED CODE | | SECTIONS. THE CODE REQUIRES CALCULATIONS, NOT A VAGUE | | NOTE THAT DOES NOT PROVIDE THE REQUIRED INFORMATION. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|