2020-03-06 05:55:21 | 1) SUBMIT A GAS RISER DIAGRAM WITH LEGIBLE INFORMATION | | ON IT. I CANNOT READ SOME OF THE PIPE SIZES BECAUSE THE | | SIZES ARE WRITTEN SO SMALL AND THEY ARE ILLEGIBLE. GO | | OVER THE LINES ON THE RISER. A COUPLE OF THEM ARE VERY | | LIGHT.WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SHOW THE CORRESPONDING EHD (EQUIVALENT HYDRAULIC | | DIAMETER) FOR THE STANDARD PIPE SIZES FOR THE | | CORRUGATED STAINLEASS STEEL TUBING. 2017 FBC-FUEL GAS | | SEC. 402.1. | | 3) COMBUSTION AIR IS REQUIRED FOR THE COOKTOP AND THE | | DRYER. PROVIDE VERIFICATION & CALCULATIONS HOW THE | | REQUIREMENTS ARE BEING MET.PROVIDE THE CODE SECTIONS | | FROM THE GAS CODE THAT YOU ARE USING IN THE DESIGN OF | | THE COMBUSTION AIR REQUIREMENTS. WPB AMEND. TO FBC SEC. | | 107.2.1, FBC-FUEL GAS SEC.304.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | | | |
|