Plan Review Notes
Plan Review Notes For Permit 20030156
Permit Number 20030156
Review Stop G
Sequence Number 1
Notes
Date Text
2020-03-06 05:55:211) SUBMIT A GAS RISER DIAGRAM WITH LEGIBLE INFORMATION
 ON IT. I CANNOT READ SOME OF THE PIPE SIZES BECAUSE THE
 SIZES ARE WRITTEN SO SMALL AND THEY ARE ILLEGIBLE. GO
 OVER THE LINES ON THE RISER. A COUPLE OF THEM ARE VERY
 LIGHT.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE CORRESPONDING EHD (EQUIVALENT HYDRAULIC
 DIAMETER) FOR THE STANDARD PIPE SIZES FOR THE
 CORRUGATED STAINLEASS STEEL TUBING. 2017 FBC-FUEL GAS
 SEC. 402.1.
 3) COMBUSTION AIR IS REQUIRED FOR THE COOKTOP AND THE
 DRYER. PROVIDE VERIFICATION & CALCULATIONS HOW THE
 REQUIREMENTS ARE BEING MET.PROVIDE THE CODE SECTIONS
 FROM THE GAS CODE THAT YOU ARE USING IN THE DESIGN OF
 THE COMBUSTION AIR REQUIREMENTS. WPB AMEND. TO FBC SEC.
 107.2.1, FBC-FUEL GAS SEC.304.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  