Plan Review Notes
Plan Review Notes For Permit 20030124
Permit Number 20030124
Review Stop P
Sequence Number 1
Notes
Date Text
2020-03-11 09:01:171) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE OIL-GUARD SYSTEM. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SHT. P000 - PUMP SCHEDULE - A FULL OPEN VALVE IS
 REQUIRED ON THE DISCHARGE SIDE OF THE CHECK VALVE IN
 THE PUMP OR EJECTOR DISCHARGE PIPING BETWEEN THE PUMP
 OR EJECTOR AND THE GRAVITY DRAINAGE SYSTEM.
 FBC-PLUMBING SEC. 712.2,1113.1.4.
 3) SHOW THE DIMENSIONS OF THE SUMP PIT ON SHT.P000. THE
 SUMP PIT SHALL COMPLY WITH FBC-PLUMBING SEC.1113.1.2 AS
 A MINIMUM.
 4) THERE ARE TWO COPIES OF SHT. P000. REMOVE THE OLD
 SHEET FROM THIS SUBMITTAL. WPB AMEND. TO FBC SEC.
 107.2.1.
 5) SHT. P000 - SHOW THE REQUIRED FULL OPEN VALVE ON THE
 SUMP DETAIL.
 6) SHTS. P101 & P102 - SOME OF THE STORM DRAINS ARE
 SHOWN AS 6 INCH ON THE PLAN VIEW YET THE STORM
 ISOMETRIC TYPICAL DECK DRAIN SECTION ONLY SHOWS 4 INCH
 PIPE. CLARIFY.
 7) SHT. P102 - THERE IS A NOTE AT EACH STAIRWELL THAT
 STATES "SHEET FLOW DOWN TO FIRST LEVEL FROM COVERED
 STAIRWELL.REFERENCE CIVIL PLANS FOR STORM DRAINAGE."
 THERE IS NO INFORMATION REGARDING THIS ON THE CIVIL
 DRAWINGS IN THIS SUBMITTAL. CLARIFY THIS NOTE.WPB
 AMEND. TO FBC SEC. 107.2.1.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE SUMP PUMP. WPB AMEND. TO FBC SEC.
 107.2.1.
 9) SHT. P000 - SUMP PUMP DETAIL STILL SHOWS THE PUMP
 DISCHARGE LINE DIRECTLY CONNECTED TO THE STORM SYSTEM.
 THIS DISCHARGE LINE SHALL BE INDIRECTLY CONNECTED TO
 THE SANITARY SYSTEM PER FBC-PLUMBING SEC.301.6.
 10) THE SANITARY LINE THAT THE PUMP IS DISCHARGING TO
 APPARENTLY HAS BEEN ABANDONED AND IS CAPPED OFF PER ONE
 OF MY FIELD INSPECTORS. RESEARCH SHALL BE DONE AND
 DOCUMENTATION SUBMITTED ON THIS LINE AND VERIFIED BY
 THE DESIGN PROFESSIONAL AND CONTRACTOR THAT THIS LINE
 IS STILL ACTIVE.WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  