2020-03-09 12:02:54 | 03/09/20 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE PLAN IS TOO SMALL TO READ NOTES, PLANS SHALL BE |
| DRAWN TO A MINIMUM 1/8" INCH SCALE PER THE WPB |
| AMENDMENT TO FBC SEC. 107.2.1.3 QUALITY OF BUILDING |
| PLANS. |
| |
| 2. THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| DIMENSIONS; AND ALL EXTERIOR ELEVATIONS IF APPLICABLE |
| PER THE FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS. |
| |
| 3. IF IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED UNLESS THE APPLICANT CAN SHOW DETAILED, QUANTITY |
| ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING |
| LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING |
| OFFICIAL. FOR PERMITTING PURPOSES, THE VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND |
| DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; |
| EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET |
| BY THE BUILDING OFFICIAL. |
| |
| 4. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) |
| ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.001, FLORIDA STATUTE 471. WPB AMENDMENTS TO |
| THE FBC SEC. 107.1 GENERAL. |
| |
| 5. PLEASE NOTE ON PLANS THAT BACKFLOW WILL BE UNDER A |
| SEPARATE PERMIT PER THE 2017 FBC WPB A 105.1. |
| |
| 6. A BUILDING AND ELECTRICAL PERMIT IS REQUIRED BY A |
| LICENSED CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| 7. PLEASE GIVE THE LEVEL OF ALTERATION PER 2017 FLORIDA |
| EXISTING BUILDING CODE 301.1. |
| |
| 8. PROVIDE MINIMUM SANITARY FACILITIES ACCORDING TO |
| 2017 FBC P TABLE 403.1. |
| |
| 9. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE |
| LINING FBC R 2709.2. |
| |
| 10. PLEASE SHOW DETAIL SHOWER PAN MUST HAVE A SLOPED |
| MORTAR BED THAT IS PRE-PITCHED BENEATH PRIOR TO LINER |
| INSTALLATION OF 1/4" IN PER FOOT TOWARD THE DRAIN, MUST |
| HAVE DAM CORNER, BACKING AROUND THE PERIMETER AND |
| BEFORE FINAL MORTAR APPLICATION PLACE SOME PEA GRAVEL |
| OVER WEEP HOLES SO THE MORTAR DOES NOT COVER THEM PER |
| MANUFACTURES SPECIFICATIONS. |
| |
| 11. WHEN CHANGING TUB TO THE SHOWER WILL THERE BE A |
| VALVE REPLACEMENT AND IF SO, IT MUST COMPLY WITH 2017 |
| FBC P SECTION 424.3. PLEASE PROVIDE A SPECIFICATION FOR |
| THE SHOWER VALVE TYPE THAT COMPLIES. WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |