2020-03-02 16:12:23RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R6
 SUBMITTED:
 INSULATED SYSTEM W-2 IS NOT APPLICABLE FOR THE PROPOSED
 APPLICATION. ACCORDING TO SEC. R301.2.1.4
 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE
 "C" NOT EXPOSURE "B" AS CIRCLED ON PRODUCT APPROVAL
 SUBMITTED. REVISE AS REQUIRED.
 ALSO, TABLE 2 OF W-2 SYSTEM ON PAGE 7 OF 14 INDICATES
 N/A FOR ROOF ZONE #3. THEREFORE, THIS SYSTEM CAN NOT BE
 USED. REVISE AS REQUIRED. NEED AN INSULATED ROOF
 ASSEMBLY THAT ALLOWS NAIL ENHANCEMENT AT PERIMETER AND
 CORNER AREAS FOR A BUILDING WITH THE SPECIFIED ROOF
 HEIGHT OF THIS BUILDING. SPECIFIED.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER