2020-03-23 11:25:49 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE |
| REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS |
| APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT. |
| |
| 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF |
| EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT |
| ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| AFFIXED TO THE DOOR LEAF. |
| (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| HAND IN THE DIRECTION OF EGRESS. |
| (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE |
| DIRECTION OF EGRESS. |
| (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS |
| CONTROL SYSTEM UNITS. |
| |
| |
| |
| 7.2.1.6* SPECIAL LOCKING ARRANGEMENTS. |
| 7.2.1.6.1 DELAYED-EGRESS LOCKING SYSTEMS. |
| 7.2.1.6.1.1 APPROVED, LISTED, DELAYED-EGRESS LOCKING |
| SYSTEMS SHALL BE PERMITTED TO BE INSTALLED ON DOOR |
| ASSEMBLIES SERVING LOW AND ORDINARY HAZARD CONTENTS IN |
| BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| ACCORDANCE WITH SECTION |
| 9.6 OR AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER |
| SYSTEM IN ACCORDANCE WITH SECTION 9.7, AND WHERE |
| PERMITTED IN CHAPTERS 11 THROUGH 43, PROVIDED THAT ALL |
| OF THE FOLLOWING CRITERIA ARE MET: |
| (1) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF |
| EGRESS UPON ACTUATION OF ONE OF THE FOLLOWING: |
| (A) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 9.7 |
| (B) NOT MORE THAN ONE HEAT DETECTOR OF AN APPROVED, |
| SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| ACCORDANCE WITH SECTION 9.6 |
| (C) NOT MORE THAN TWO SMOKE DETECTORS OF AN APPROVED, |
| SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| ACCORDANCE WITH SECTION 9.6 |
| (2) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF |
| EGRESS UPON LOSS OF POWER CONTROLLING THE LOCK OR |
| LOCKING MECHANISM. |
| (3)* AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK IN |
| THE DIRECTION OF EGRESS WITHIN 15 SECONDS, OR 30 |
| SECONDS WHERE APPROVED BY THE AUTHORITY HAVING |
| JURISDICTION, UPON APPLICATION OF A FORCE TO THE |
| RELEASE DEVICE REQUIRED IN 7.2.1.5.10 UNDER ALL OF THE |
| FOLLOWING CONDITIONS: |
| (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF |
| (67 N). |
| (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY |
| APPLIED FOR MORE THAN 3 SECONDS. |
| (C) THE INITIATION OF THE RELEASE PROCESS SHALL |
| ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR |
| OPENING. |
| (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION |
| OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY |
| MANUAL MEANS ONLY. |
| (4)* A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT |
| LESS THAN 1 IN. (25 MM) HIGH AND NOT LESS THAN 1?8 IN. |
| (3.2 MM) IN STROKE WIDTH ON A CONTRASTING BACKGROUND |
| THAT READS AS FOLLOWS SHALL BE LOCATED ON THE DOOR LEAF |
| ADJACENT TO THE RELEASE DEVICE IN THE DIRECTION OF |
| EGRESS: |
| PUSH UNTIL ALARM SOUNDS |
| DOOR CAN BE OPENED IN 15 SECONDS |
| (5) THE EGRESS SIDE OF DOORS EQUIPPED WITH |
| DELAYED-EGRESS LOCKS SHALL BE PROVIDED WITH EMERGENCY |
| LIGHTING IN ACCORDANCE WITH SECTION 7.9. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |