Plan Review Notes
Plan Review Notes For Permit 20021276
Permit Number 20021276
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2020-03-23 11:25:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
  
  
 7.2.1.6* SPECIAL LOCKING ARRANGEMENTS.
 7.2.1.6.1 DELAYED-EGRESS LOCKING SYSTEMS.
 7.2.1.6.1.1 APPROVED, LISTED, DELAYED-EGRESS LOCKING
 SYSTEMS SHALL BE PERMITTED TO BE INSTALLED ON DOOR
 ASSEMBLIES SERVING LOW AND ORDINARY HAZARD CONTENTS IN
 BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH SECTION
 9.6 OR AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION 9.7, AND WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43, PROVIDED THAT ALL
 OF THE FOLLOWING CRITERIA ARE MET:
 (1) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF
 EGRESS UPON ACTUATION OF ONE OF THE FOLLOWING:
 (A) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7
 (B) NOT MORE THAN ONE HEAT DETECTOR OF AN APPROVED,
 SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH SECTION 9.6
 (C) NOT MORE THAN TWO SMOKE DETECTORS OF AN APPROVED,
 SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH SECTION 9.6
 (2) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF
 EGRESS UPON LOSS OF POWER CONTROLLING THE LOCK OR
 LOCKING MECHANISM.
 (3)* AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK IN
 THE DIRECTION OF EGRESS WITHIN 15 SECONDS, OR 30
 SECONDS WHERE APPROVED BY THE AUTHORITY HAVING
 JURISDICTION, UPON APPLICATION OF A FORCE TO THE
 RELEASE DEVICE REQUIRED IN 7.2.1.5.10 UNDER ALL OF THE
 FOLLOWING CONDITIONS:
 (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF
 (67 N).
 (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY
 APPLIED FOR MORE THAN 3 SECONDS.
 (C) THE INITIATION OF THE RELEASE PROCESS SHALL
 ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR
 OPENING.
 (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION
 OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY
 MANUAL MEANS ONLY.
 (4)* A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT
 LESS THAN 1 IN. (25 MM) HIGH AND NOT LESS THAN 1?8 IN.
 (3.2 MM) IN STROKE WIDTH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS SHALL BE LOCATED ON THE DOOR LEAF
 ADJACENT TO THE RELEASE DEVICE IN THE DIRECTION OF
 EGRESS:
 PUSH UNTIL ALARM SOUNDS
 DOOR CAN BE OPENED IN 15 SECONDS
 (5) THE EGRESS SIDE OF DOORS EQUIPPED WITH
 DELAYED-EGRESS LOCKS SHALL BE PROVIDED WITH EMERGENCY
 LIGHTING IN ACCORDANCE WITH SECTION 7.9.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved