2020-03-04 14:01:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE |
| REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS |
| APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT. |
| |
| 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF |
| EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT |
| ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| AFFIXED TO THE DOOR LEAF. |
| (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| HAND IN THE DIRECTION OF EGRESS. |
| (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE |
| DIRECTION OF EGRESS. |
| (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS |
| CONTROL SYSTEM UNITS. |
| |
| |
| 7.2.1.6* SPECIAL LOCKING ARRANGEMENTS. |
| 7.2.1.6.1 DELAYED-EGRESS LOCKING SYSTEMS. |
| 7.2.1.6.1.1 APPROVED, LISTED, DELAYED-EGRESS LOCKING |
| SYSTEMS SHALL BE PERMITTED TO BE INSTALLED ON DOOR |
| ASSEMBLIES SERVING LOW AND ORDINARY HAZARD CONTENTS IN |
| BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| ACCORDANCE WITH SECTION |
| 9.6 OR AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER |
| SYSTEM IN ACCORDANCE WITH SECTION 9.7, AND WHERE |
| PERMITTED IN CHAPTERS 11 THROUGH 43, PROVIDED THAT ALL |
| OF THE FOLLOWING CRITERIA ARE MET: |
| (1) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF |
| EGRESS UPON ACTUATION OF ONE OF THE FOLLOWING: |
| (A) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 9.7 |
| (B) NOT MORE THAN ONE HEAT DETECTOR OF AN APPROVED, |
| SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| ACCORDANCE WITH SECTION 9.6 |
| (C) NOT MORE THAN TWO SMOKE DETECTORS OF AN APPROVED, |
| SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| ACCORDANCE WITH SECTION 9.6 |
| (2) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF |
| EGRESS UPON LOSS OF POWER CONTROLLING THE LOCK OR |
| LOCKING MECHANISM. |
| (3)* AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK IN |
| THE DIRECTION OF EGRESS WITHIN 15 SECONDS, OR 30 |
| SECONDS WHERE APPROVED BY THE AUTHORITY HAVING |
| JURISDICTION, UPON APPLICATION OF A FORCE TO THE |
| RELEASE DEVICE REQUIRED IN 7.2.1.5.10 UNDER ALL OF THE |
| FOLLOWING CONDITIONS: |
| (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF |
| (67 N). |
| (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY |
| APPLIED FOR MORE THAN 3 SECONDS. |
| (C) THE INITIATION OF THE RELEASE PROCESS SHALL |
| ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR |
| OPENING. |
| (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION |
| OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY |
| MANUAL MEANS ONLY. |
| (4)* A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT |
| LESS THAN 1 IN. (25 MM) HIGH AND NOT LESS THAN 1?8 IN. |
| (3.2 MM) IN STROKE WIDTH ON A CONTRASTING BACKGROUND |
| THAT READS AS FOLLOWS SHALL BE LOCATED ON THE DOOR LEAF |
| ADJACENT TO THE RELEASE DEVICE IN THE DIRECTION OF |
| EGRESS: |
| PUSH UNTIL ALARM SOUNDS |
| DOOR CAN BE OPENED IN 15 SECONDS |
| (5) THE EGRESS SIDE OF DOORS EQUIPPED WITH |
| DELAYED-EGRESS LOCKS SHALL BE PROVIDED WITH EMERGENCY |
| LIGHTING IN ACCORDANCE WITH SECTION 7.9. |
| |
| |
| 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES. |
| WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR |
| ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO |
| BE EQUIPPED WITH ELECTRICAL LOCK HARDWARE THAT PREVENTS |
| EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE |
| MET: |
| (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| ARRANGED TO UNLOCK THE DOOR LEAF IN THE DIRECTION OF |
| EGRESS UPON DETECTION OF AN APPROACHING OCCUPANT. |
| (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE |
| DIRECTION OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR |
| TO THE PART OF THE ACCESS CONTROL SYSTEM THAT LOCKS THE |
| DOOR LEAVES. |
| (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE |
| DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| COMPLYING WITH ALL OF THE FOLLOWING CRITERIA: |
| (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE |
| EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM ) |
| VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM) |
| OF THE SECURED DOOR OPENINGS. |
| (B) THE MANUAL RELEASE DEVICE SHALL BE READILY |
| ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS |
| AS FOLLOWS: PUSH TO EXIT. |
| (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK |
| INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS .AND THE |
| LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30 |
| SECONDS. |
| (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE |
| SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY |
| UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND |
| THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE |
| FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY |
| RESET. |
| (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT |
| ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM |
| SPECIFIED IN 7.2.1.6.2 (4) SHALL NOT BE REQUIRED TO |
| UNLOCK THE DOOR LEAVES. |
| (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR |
| FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY |
| UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND |
| THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE |
| FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY |
| RESET. |
| (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS, |
| OTHER THAN EXISTING ACCESS-CONTROLLED EGRESS DOORS, |
| SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE |
| WITH SECTION 7.9. |
| |
| PETER LEDUC |