Plan Review Notes For Permit 20021265 |
Permit Number |
20021265 |
|
Review Stop |
NFIP |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-04-24 17:05:55 | PLAN REVIEW - NFIP | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER ? BUILDING - PX3169 | | PLANS EXAMINER ? 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW - CONSTRUCTION DRAWING ELEVATION CERTIFICATE | | - EC | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. REFERENCE C2 (E) OF EC. LOWEST ELEVATION OF | | EQUIPMENT SERVICING THE BUILDING SHALL BE THE DFE OF | | 8.0' NAVD. | | PLEASE CORRECT | | | | 2. REFERENCE B9 OF EC. PROPERTY IS LOCATED IN FLOOD | | ZONE AE WITH TWO BASE FLOOD ELEVATIONS. B9 SHOULD STATE | | 6.0' & 7.0'. | | PLEASE CORRECT | | | | |
|