2020-04-24 15:59:18 | PLAN REVIEW - ELECTRICAL |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER ? BUILDING - PX3169 |
| PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 2ND REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. |
| PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) PAGE A.04 |
| |
| PANEL "G" WILL REQUIRE A GROUNDING ELECTRODE SYSTEM TO |
| BE INSTALLED 250.32(A) - CORRECTED |
| |
| MDP 400A PANEL WILL NEED A LOAD CALCULATION FOR THE |
| ADDED LOAD FROM PANEL "G" (NOT ADDRESSED) |
| |
| NEW COMMENTS: |
| |
| 2) THE FUTURE PANEL "G" 60A ON THE RISER DIAGRAHM IS |
| NOT LABLED. THE NEW PANEL SCHEDULE AND LOAD CALC'S FOR |
| THE PROPOSED GARAGE IS LABLED PANEL "F". |
| PLEASE CLARIFY. |
| |
| 3) THE PANEL SCHEDULE TO THE LEFT OF THE NEW GARAGE |
| PANEL IS NOT LABLED. IS THIS THE MDP 400A PANEL? ALL |
| CIRCUTS ARE LABLED CIR# 1 EXCEPT FOR 2 LABLED #2. |
| PLEASE LABLE CIRCUTS CORRECTLY. |
| |
| 4) THE UNLABLED PANEL SCHEDULE SHOWS THE CAR CHARGER |
| CIRCUT WITH A 2 POLE 50A OCP WITH 12000 WATTS. THE NEW |
| GARAGE PANEL SHOWS THE CAR CHARGER CIRCUT WITH A 2 POLE |
| 50A OCP WITH 24000 WATTS. |
| PLEASE CLARIFY. |
| |
| 5) THE UNLABLED SCHEDULE SHOWS THE GARAGE DOOR OPENER |
| WITH A 20A OCP. THE NEW GARAGE SCHEDULE SHOWS THE |
| GARAGE DOOR OPENER WITH A 15A OCP. |
| PLEASE CLARIFY. |
| |
| |
| |
| |
| |