2020-04-24 15:59:18PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGE A.04
  
 PANEL "G" WILL REQUIRE A GROUNDING ELECTRODE SYSTEM TO
 BE INSTALLED 250.32(A) - CORRECTED
  
 MDP 400A PANEL WILL NEED A LOAD CALCULATION FOR THE
 ADDED LOAD FROM PANEL "G" (NOT ADDRESSED)
  
 NEW COMMENTS:
  
 2) THE FUTURE PANEL "G" 60A ON THE RISER DIAGRAHM IS
 NOT LABLED. THE NEW PANEL SCHEDULE AND LOAD CALC'S FOR
 THE PROPOSED GARAGE IS LABLED PANEL "F".
 PLEASE CLARIFY.
  
 3) THE PANEL SCHEDULE TO THE LEFT OF THE NEW GARAGE
 PANEL IS NOT LABLED. IS THIS THE MDP 400A PANEL? ALL
 CIRCUTS ARE LABLED CIR# 1 EXCEPT FOR 2 LABLED #2.
 PLEASE LABLE CIRCUTS CORRECTLY.
  
 4) THE UNLABLED PANEL SCHEDULE SHOWS THE CAR CHARGER
 CIRCUT WITH A 2 POLE 50A OCP WITH 12000 WATTS. THE NEW
 GARAGE PANEL SHOWS THE CAR CHARGER CIRCUT WITH A 2 POLE
 50A OCP WITH 24000 WATTS.
 PLEASE CLARIFY.
  
 5) THE UNLABLED SCHEDULE SHOWS THE GARAGE DOOR OPENER
 WITH A 20A OCP. THE NEW GARAGE SCHEDULE SHOWS THE
 GARAGE DOOR OPENER WITH A 15A OCP.
 PLEASE CLARIFY.
  
  
  
  
  