2020-04-24 16:40:54 | PLAN REVIEW - BUILDING | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER ? BUILDING - PX3169 | | PLANS EXAMINER ? 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. NOTE ON PAGE A.03 STATES ALL EQUIPMENT SHALL BE AT | | BASE FLOOD ELEVATION (BFE) 8.0' NAVD. THE BASE FLOOD | | ELEVATION FOR THIS STRUCTURE IS 6.0' NAVD. COMMENT | | SHOULD STATE THE EQUIPMENT SHALL BE AT THE DESIGN FLOOD | | ELEVATION (DFE) 8.0' NAVD. | | PLEASE CORRECT | | | | 2. NOTE ON PAGE A.10 STATES EQUIPMENT SHALL BE AT 5.7' | | NAVD. THE EQUIPMENT SERVICING THE STRUCTURE SHALL BE AT | | THE DESIGN FLOOD ELEVATION (DFE) OF 8.0' NAVD. | | PLEASE CORRECT. | | | | 3. NOTE ON PAGE A.10 STATES THE GENERATOR PAD SHALL BE | | AT BFE OF 8.0' NAVD. NOTE SHOULD STATE GENERATOR SHALL | | BE AT DFE OF 8.0' NAVD. | | PLEASE CORRECT. | | | | |
|