2020-04-24 16:40:54PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NOTE ON PAGE A.03 STATES ALL EQUIPMENT SHALL BE AT
 BASE FLOOD ELEVATION (BFE) 8.0' NAVD. THE BASE FLOOD
 ELEVATION FOR THIS STRUCTURE IS 6.0' NAVD. COMMENT
 SHOULD STATE THE EQUIPMENT SHALL BE AT THE DESIGN FLOOD
 ELEVATION (DFE) 8.0' NAVD.
 PLEASE CORRECT
  
 2. NOTE ON PAGE A.10 STATES EQUIPMENT SHALL BE AT 5.7'
 NAVD. THE EQUIPMENT SERVICING THE STRUCTURE SHALL BE AT
 THE DESIGN FLOOD ELEVATION (DFE) OF 8.0' NAVD.
 PLEASE CORRECT.
  
 3. NOTE ON PAGE A.10 STATES THE GENERATOR PAD SHALL BE
 AT BFE OF 8.0' NAVD. NOTE SHOULD STATE GENERATOR SHALL
 BE AT DFE OF 8.0' NAVD.
 PLEASE CORRECT.
  
  