2020-03-28 09:12:10 | PLAN REVIEW - NFIP |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA) FINISHED FLOOR ELEVATION OF PROPOSED GARAGE IS |
| 5.28 NAVD - SEE PLAN PAGE S.02. |
| THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS |
| AE WITH BASE FLOOD ELEVATIONS (BFE) OF 6FT. & 7FT. THE |
| CITY OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN |
| ADDITIONAL 24 INCHES OF FREEBOARD REQUIRING THE DESIGN |
| FLOOD ELEVATION (DFE) TO BE 8. 0 FEET OR 9.0 FEET |
| DEPENDING ON LOCATION OF STRUCTURE. THE PROPOSED GARAGE |
| IS LOCATED IN AE ZONE WITH A 6FT. BASE FLOOD ELEVATION |
| (BFE). PLEASE NOTE THIS INFORMATION ON YOUR PLANS. |
| |
| A CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC) IS |
| REQUIRED AT TIME OF PERMIT APPLICATION. PERMIT WILL NOT |
| BE ISSUED UNTIL A COMPLIANT EC HAS BEEN REVIEWED AND |
| APPROVED. |
| NOTE: ALL NEW OR RE-LOCATED EQUIPMENT SERVICING THE |
| PROPOSED ENCLOSED BUILDING ON THIS SITE ARE REQUIRED TO |
| BE AT OR ABOVE 8 FEET NAVD. |
| |
| AN UNDER CONSTRUCTION EC AND FORMBOARD SURVEY WITH |
| FINISHED FLOOR ELEVATION IS REQUIRED. AT PLACEMENT OF |
| 1ST FLOOR. |
| |
| A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| THIS EC MAY BE SUBMITTED FOR REVIEW PRIOR TO BUILDING |
| FINAL. |
| |
| 2. G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION. |
| FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION |
| SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO |
| THE FOLLOWING: |
| |
| 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY |
| WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS |
| TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF |
| FLOODWATERS. |
| |
| R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION. |
| ENCLOSED AREAS, INCLUDING CRAWL SPACES, THAT ARE BELOW |
| THE DESIGN FLOOD ELEVATION SHALL: |
| 1.BE USED SOLELY FOR PARKING OF VEHICLES, BUILDING |
| ACCESS OR STORAGE. |
| 2.BE PROVIDED WITH FLOOD OPENINGS THAT MEET THE |
| FOLLOWING CRITERIA AND ARE INSTALLED IN ACCORDANCE WITH |
| SECTION R322.2.2.1: |
| 2.1.THE TOTAL NET AREA OF NON-ENGINEERED OPENINGS |
| SHALL BE NOT LESS THAN 1 SQUARE INCH (645 MM2) FOR EACH |
| SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE THE |
| ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE |
| ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS |
| ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS |
| SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN |
| PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL |
| PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON |
| EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND |
| EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF |
| ASCE 24. |
| 2.2.OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM) |
| IN ANY DIRECTION IN THE PLANE OF THE WALL. |
| 2.3.THE PRESENCE OF LOUVERS, BLADES, SCREENS AND |
| FACEPLATES OR OTHER COVERS AND DEVICES SHALL ALLOW THE |
| AUTOMATIC FLOW OF FLOODWATER INTO AND OUT OF THE |
| ENCLOSED AREAS AND SHALL BE ACCOUNTED FOR IN THE |
| DETERMINATION OF THE NET OPEN AREA. |
| |
| |
| |
| |
| |
| |