2020-03-23 13:26:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGE A.04
  
 PANEL "G" WILL REQUIRE A GROUNDING ELECTRODE SYSTEM TO
 BE INSTALLED 250.32(A)
  
 MDP 400A PANEL WILL NEED A LOAD CALCULATION FOR THE
 ADDED LOAD FROM PANEL "G"
  
  