Date |
Text |
2020-03-02 03:33:20 | 1) THE DESCRIPTION OF WORK ON THE APPLICATION STATES |
| "NEW PLUMBING " AND SPECS FOR A BACKFLOW DEVICE HAVE |
| BEEN SUBMITTED. THE DESCRIPTION OF WORK ON THE |
| APPLICATION IS SO VAGUE I CANNOT APPROVE THIS PERMIT. |
| IS THERE ANY OTHER PLUMBING WORK BEING DONE? PLACE A |
| CLEAR DESCRIPTION ON THE PERMIT APPLICATION OF THE |
| ENTIRE SCOPE OF WORK TO BE DONE.WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 2) THE MAKE, MODEL AND SIZE OF THE DEVICE SHALL BE |
| NOTED IN THE DESCRIPTION OF WORK SECTION ON THE PERMIT |
| APPLICATION. WPB AMEND. TO FBC SEC. 107.2.1. |
| 3) ON WHAT TYPE OF SYSTEM IS THE DEVICE BEING INSTALLED |
| ( DOMESTIC WATER, IRRIGATION)? PLACE THIS INFORMATION |
| ON THE PERMIT APPLICATION. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 4) IS THIS DEVICE BEING INSTALLED AT THE WATER METER ( |
| CONTAINMENT) OR IS IT BEING INSTALLED ON A BRANCH OFF |
| THE DOMESTIC LINE (ISOLATION)? PLACE THIS INFORMATION |
| ON THE PERMIT APPLICATION. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 5) PIPING FROM THE WATER METER TO THE INLET OF THE |
| BACKFLOW ASSEMBLY SHALL BE TYPE "K" OR "L" COPPER, |
| BRASS OR STAINLESS STEEL PER CITY OF WEST PALM BEACH |
| STANDARD DETAIL DRAWING WS-11. |
| 6) THE VALUE NOTED ON THE APPLICATION SEEMS LOW. SUBMIT |
| A DETAILED, QUANTITY ESTIMATE OR BONA FIDE SIGNED |
| CONTRACT FOR THIS WORK. WPB AMEND. TO FBC SEC. 109.3. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |