Plan Review Notes For Permit 20021198 |
Permit Number |
20021198 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-20 08:19:49 | AWNING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE PROVIDE FOUNDATION, FRAMING AND ATTACHMENT | | DETAILS. THE AWNING IS SUBJECT TO WIND LOADS PER FBC | | 3105.3 PLEASE PROVIDE THE STRUCTURAL CALCULATIONS | | REQUIRED FOR THESE LOADS OR HAVE THE DETAILS PREPARED | | AND SIGNED AND SEALED BY AN ARCHITECT OR ENGINEER (WIND | | DESIGN CRITERIA WILL NEED TO BE SHOWN ON THE DRAWINGS | | 1603.1.4) | | 2) PLEASE PROVIDE THE FIRE CERTIFICATE SHOWING | | COMPLIANCE WITH FBC 3105.3.4.1 FABRIC USED FOR AWNINGS | | OR FABRIC-COVERED FRAMES SHALL MEET THE FLAME | | PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A | | FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN TESTED IN | | ACCORDANCE WITH ASTM E84 OR UL 723. |
|