Plan Review Notes For Permit 20021198
Permit Number 20021198
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-20 08:19:49AWNING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE FOUNDATION, FRAMING AND ATTACHMENT
 DETAILS. THE AWNING IS SUBJECT TO WIND LOADS PER FBC
 3105.3 PLEASE PROVIDE THE STRUCTURAL CALCULATIONS
 REQUIRED FOR THESE LOADS OR HAVE THE DETAILS PREPARED
 AND SIGNED AND SEALED BY AN ARCHITECT OR ENGINEER (WIND
 DESIGN CRITERIA WILL NEED TO BE SHOWN ON THE DRAWINGS
 1603.1.4)
 2) PLEASE PROVIDE THE FIRE CERTIFICATE SHOWING
 COMPLIANCE WITH FBC 3105.3.4.1 FABRIC USED FOR AWNINGS
 OR FABRIC-COVERED FRAMES SHALL MEET THE FLAME
 PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A
 FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN TESTED IN
 ACCORDANCE WITH ASTM E84 OR UL 723.