2020-03-03 13:57:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20021115
 ADD: 1200 S. FLAGLER DR. SUITE: 303
 CONT: CAMBRIDGE CONSTRUCTION LLC
 TEL: 561-784-3722
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 03/2020
 ACTION: DENIED
  
 1) W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR TO BE LICENSED IN
 THE TRADE THAT THEY WILL BE CREATING THE PLANS TO BE
 SUBMITTED TO THE BUILDING DEPARTMENT. FOR EACH TRADE
 THE CONTRACTOR RESPONSIBLE FOR THE PLAN MUST PRINT
 THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER.
  
 2) THE SUBMITTED FLOOR PLAN HAS A NOTE TO DROP THE
 CEILINGS IN BOTH BEDROOMS TO ACCOMMODATE NEW CEILING
 FANS. THE PLANS ARE SILENT AS TO HOW FAR THE CEILINGS
 ARE TO BE DROPPED. THE PLANS DO NOT INDICATE THE TYPE
 OF ANCHOR TO BE FASTENED INTO THE CONCRETE DECK ABOVE,
 DEPTH OF FASTENER INTO THE CONCRETE DECK, IS THE
 CONCRETE DECK POST TENSION?
 PROVIDE THE TYPE OF FRAMING MEMBER TO BE INSTALLED SIZE
 AND SPACING, PLEASE NOT THIS IS A HIGHRISE AND ALL
 FRAMING MEMBERS ARE TO BE NON-COMBUSTIBLE. PLEASE
 PROVIDE THE JOIST SPACING IN INCHES, THE SPAN, IS THE
 MID-POINT UNSUPPORTED OR IS THERE A MID-SPAN SUPPORT.
 PLEASE PROVIDE THE TYPE OF CEILING MATERIAL AND
 THICKNESS AND ALLOWABLE SPANS? 2017 FBC-B 2508.1/ TABLE
 2508.1 STEEL FRAMING FOR GYPSUM BOARD ASTM C754.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER