 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?ANCHOR SPACING? PROVIDE INFORMATION FROM SHEET
 13 FL1850-R11. EXAMPLE SUBSTRATE POURED CONCRETE,
 MAXIMUM SPAN 8?-0?, A.S.D DESIGN NEGATIVE PRESSURE
 RATING (PSF) 120; CEILING MOUNT (G) USING TAPCONS WITH
 ADVANCED THREADFORM TECHNOLOGY ANCHOR SPACING IS 5.5?
 MAXIMUM. SECOND REQUEST.
  