Plan Review Notes
Plan Review Notes For Permit 20021087
Permit Number 20021087
Review Stop B
Sequence Number 2
Notes
Date Text
2020-03-16 10:42:59PROVISO:
 SEPARATE FIRE SPRINKLER PERMIT REQUIRED.
  
  
 03/16/2020 TALKED TO JESSICA (ARCHITECT):
 1) USING 4" STUD FOR FIRE RATED HORIZONTAL SHAFT
 ASSEMBLY.
 2) FIRE RATED WALL ASSEMBLY COULD NOT GO ALL THE WAY UP
 BECAUSE OF ISSUES WITH THE DUCTWORK. THE HORIZONTAL
 SHAFT ASSEMBLY WAS USED ISOLATE THE ROOM FROM THE
 CORRIDOR.
 NOTE: ACCORDING TO TABLE 1020.1 CORRIDOR FIRE
 RESISTANCE IS NOT REQUIRED IF THE BUILDING IS FULLY
 SPRINKLERED.