Plan Review Notes For Permit 20021087 |
Permit Number |
20021087 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-03-13 20:02:03 | REVISION BUILDING REVIEW CHECKLIST. | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- SPECIFY THE SIZE AND ORIENTATION OF THE I STUDS TO | | VERIFY COMPLIANCE WITH THE MAXIMUM HORIZONTAL SPAN FOR | | I-STUD ASSEMBLIES AS SHOWN ON THE TABLE OF USG ASSEMBLY | | SUBMITTED ON SHEET A2.1.1. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | 2- CLARIFY WHY THE FIRE RATED PARTITION WAS REVISED AND | | DOESN'T GO ALL THE WAY UP TO THE BOTTOM OF THE CEILING. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|