2020-02-28 14:38:32RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R23
 SUBMITTED:
 SELECTED ASSEMBLY W-170 CAN NOT BE USED. THIS ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
 BONDED ASSEMBLIES NEED TO MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES. SEE NOTE #10 ON PAGE 2 OF 65 OF PRODUCT
 APPROVAL SUBMITTED.
 NEED TO SELECT ANOTHER BONDED ASSEMBLY THAT MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES
 REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. OR SELECT
 ANOTHER MECHANICALLY FASTENED ASSEMBLY THAT MEETS THE
 DESIGN FOR ALL ROOF ZONES. OR SELECT ANOTHER ASSEMBLY
 THAT ALLOWS NAIL ENHANCEMENT BY DOING RAS 117
 CALCULATIONS. IF RAS 117 CALCULATIONS ARE PROVIDED,
 THEN THEY NEED TO BE PROPERLY SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL.
  
 2- BONDED ASSEMBLIES REQUIRE FIELD UPLIFT TESTING (TAS
 124). SEE NOTE#12 ON PAGE 2 OF 65 OF FLORIDA PRODUCT
 APPROVAL SUBMITTED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,