Date |
Text |
2020-05-04 10:59:40 | 1) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER |
| FBC-FUEL GAS SEC.301.3. THE SUBMITTED SPECIFICATIONS |
| FOR THE RANGE, GRILL AND POOL HEATER DO NOT SHOW THE |
| LISTING FOR THE APPLIANCES. |
| 2) THE POOL HEATER SHALL HAVE A THERMAL EFFICIENCY OF |
| 82% PER FBC-ENERGY SEC.R403.10.4. SUBMIT VERIFICATION |
| OF COMPLIANCE. |
| 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE UNVENTED |
| GAS LOG, FIREPLACE, CLOTHES DRYERS, AND RANGE, FBC-FUEL |
| GAS SEC.304.1. THE RESPONSE FROM FAE REFERS TO SHT. |
| M1.1. THERE WAS NO SHT. M1.1 SUBMITTED. |
| 4) SUBMIT THE SPECIFICATIONS FOR THE GENERATOR THAT |
| SHOW THE MODEL OF THE GENERATOR BEING INSTALLED. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 5) THE FUEL FLOW RATE (BTU LOAD) SHOWN IN THE SUBMITTED |
| GENERATOR SPECIFICATIONS DOES NOT CORRELATE WITH THE |
| BTU LOAD OF THE GENERATOR SHOWN ON THE GAS RISER. |
| CLARIFY. |
| 6) THE GAS PLANS CALL OUT 2 DIFFERENT GAS SIZING TABLES |
| FOR THE LOW PRESSURE SYSTEM- 402.4 (1) & 402.4 (2). |
| CLARIFY. |
| 7) SHOW THE DISTANCE FROM THE MAIN GAS LINE TO THE |
| GENERATOR. |
| 8) SHOW THE DISTANCE FROM EACH REGULATOR TO THE GAS |
| APPLIANCE. INCLUDE THE DIMENSIONS OF ALL OFFSETS AND |
| DROPS TO THE APPLIANCE. THE CODE REQUIRES THE DEVELOPED |
| LENGTH. |
| 9) THE 1 1/2 INCH SCH. 40 PIPE LINE TO THE POOL HEATER, |
| FIREPLACE AND FIREPIT IS UNDERSIZED PER GAS SIZING |
| TABLE 402.4 (2). THE TABLE ALLOWS 532 MBTU'S AT THE |
| CALCULATED LENGTH AND THE PLANS SHOW 540 MBTU'S. |
| 10) THE 3/4 INCH SCH. 40 METALLIC PIPE TO THE FIREPIT |
| IS UNDERSIZED PER GAS SIZING TABLE 402.4 (2). THE TABLE |
| ALLOWS 92 MBTU'S AT THE CALCULATED LENGTH AND THE PLANS |
| SHOW 100 MBTU'S. |
| 11) THE 1 1/4 INCH LINE TO THE GENERATOR MAY BE |
| UNDERSIZED. THE DISTANCE FROM THE REGULATOR TO THE |
| GENERATOR IS REQUIRED TO DETERMINE IF THE PIPE SIZE IS |
| CODE COMPLIANT. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |