Plan Review Notes
Plan Review Notes For Permit 20021029
Permit Number 20021029
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-03-05 14:24:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 1.1 - THERE IS AN INDICATION OF OCCUPANCY AS
 GROUP B - BUSINESS.
  
 WHAT IS THE PROPOSED USE OF THE BUILDING? IT APPEARS TO
 BE MERCANTILE PER THE FLORIDA FIRE PREVENTION CODE.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS.
  
  
 2) SHEET 1.1 - THE ARE NO INDICATIONS OF ELECTICAL
 SHEETS NOR ELECTRICAL WORK
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) SHEET 3.0 - THERE IS NO INDICATIONS OF AN OCCUPANCY
 LOAD PER # 1 ABOVE.
  
 PER NFPA 101, CH 7
  
 7.3 CAPACITY OF MEANS OF EGRESS.
 7.3.1 OCCUPANT LOAD.
 7.3.1.1 SUFFICIENT CAPACITY.
 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR
 ANY STORY,
 BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL BE
 SUFFICIENT FOR THE
 OCCUPANT LOAD THEREOF.
 7.3.1.1.2 FOR OTHER THAN EXISTING MEANS OF EGRESS,
 WHERE MORE
 THAN ONE MEANS OF EGRESS IS REQUIRED, THE MEANS OF
 EGRESS SHALL BE
 OF SUCH WIDTH AND CAPACITY THAT THE LOSS OF ANY ONE
 MEANS OF
 EGRESS LEAVES AVAILABLE NOT LESS THAN 50 PERCENT OF THE
 REQUIRED
 CAPACITY.
 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY
 BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE
 NUMBER OF
 PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED
 TO THAT USE
 BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED
 IN TABLE
 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B).
 WHERE BOTH
 GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME
 OCCUPANCY,
 CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA
 FIGURE TO THE
 GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO
 THE USE FOR
 WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY
 APPLYING THE NET
 AREA FIGURE TO THE NET AREA OF THE PORTION OF THE
 BUILDING DEVOTED TO
 THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED.
  
 PROVIDE THE SIZE OF EGRESS WIDTH AND THE OCCUPANCY LOAD
 COUNT THROUGH THOSE EXITS.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 4) SHEET 3.0 - THERE IS NO INDICATIONS OF THE
 SEPARATION OF THE REQUIRED EGRESSES.
  
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5.
  
 PER # 1 ABOVE, PLEASE PROVIDE THE DIMENSION OF THE
 SEPARATION OF EGRESS
  
  
  
 5) SHEET 3.0 - THERE IS NO CLEAR EXIT SIGANGE WITH
 ILLUMINATION.
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN
 ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS
 11
 THROUGH 43.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 6) SHEET 3.0 - THERE IS NO INDICATION OF EGRESS
 LIGHTING
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND
 STRUCTURE WHERE
 REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF
 THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE
 TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS
 BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN
 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR
 SUCH PERIODS OF TIME AS ARE NECESSARY TO MAINTAIN THE
 ILLUMINATION TO THE
 MINIMUM CRITERIA VALUES HEREIN SPECIFIED.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 7) SHEET 3.0 - PER THE APPLICABLE OCCUPANCY CHAPTER
 EMERGENCY LIGHTING IS NOT INDICATED.
  
 7.9 EMERGENCY LIGHTING.
 7.9.1 GENERAL.
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE
 FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
 (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS
 ADDRESSED IN SECTION
 11.7
 (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS
 OF THIS CODE
 (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS
 (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF
 ENCLOSURES, FOR WHICH THE
 FOLLOWING ALSO APPLY:
 (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO
 INCLUDE A
 STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF
 ENCLOSURE MECHANICAL VENTILATION EQUIPMENT.
 (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED
 FOR THE
 STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER
 SUPPLY.
 (6) NEW ACCESS-CONTROLLED EGRESS DOORS IN ACCORDANCE
 WITH 7.2.1.6.2
  
 PLEASE REVIEW AND PROVIDE.
  
  
 8) SHEET 3.2 & 10.1 - THE REAR DOOR IS NOT INDICATED ON
 THE DOOR SCHEDULE, INCLUDING NO HARDWARE.
  
 PLEASE REVIEW AND CORRECT.
  
 IF THIS IS ALSO A REQUIRED EXIT DOOR, (WHICH IT
 SHOULDBW) ALL EXIT HARDWARE SHALL BE INCLUDED.
  
  
  
 9) PLEASE SECURE AND BIND ALL APPLICABLE SHEETS INTO 2
 COMPLETE SETS NOT 6 SEPARATE SHEETS.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL