2020-03-05 14:24:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET 1.1 - THERE IS AN INDICATION OF OCCUPANCY AS |
| GROUP B - BUSINESS. |
| |
| WHAT IS THE PROPOSED USE OF THE BUILDING? IT APPEARS TO |
| BE MERCANTILE PER THE FLORIDA FIRE PREVENTION CODE. |
| |
| PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS. |
| |
| |
| 2) SHEET 1.1 - THE ARE NO INDICATIONS OF ELECTICAL |
| SHEETS NOR ELECTRICAL WORK |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| 3) SHEET 3.0 - THERE IS NO INDICATIONS OF AN OCCUPANCY |
| LOAD PER # 1 ABOVE. |
| |
| PER NFPA 101, CH 7 |
| |
| 7.3 CAPACITY OF MEANS OF EGRESS. |
| 7.3.1 OCCUPANT LOAD. |
| 7.3.1.1 SUFFICIENT CAPACITY. |
| 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR |
| ANY STORY, |
| BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL BE |
| SUFFICIENT FOR THE |
| OCCUPANT LOAD THEREOF. |
| 7.3.1.1.2 FOR OTHER THAN EXISTING MEANS OF EGRESS, |
| WHERE MORE |
| THAN ONE MEANS OF EGRESS IS REQUIRED, THE MEANS OF |
| EGRESS SHALL BE |
| OF SUCH WIDTH AND CAPACITY THAT THE LOSS OF ANY ONE |
| MEANS OF |
| EGRESS LEAVES AVAILABLE NOT LESS THAN 50 PERCENT OF THE |
| REQUIRED |
| CAPACITY. |
| 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| NUMBER OF |
| PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED |
| TO THAT USE |
| BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED |
| IN TABLE |
| 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B). |
| WHERE BOTH |
| GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME |
| OCCUPANCY, |
| CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA |
| FIGURE TO THE |
| GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO |
| THE USE FOR |
| WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY |
| APPLYING THE NET |
| AREA FIGURE TO THE NET AREA OF THE PORTION OF THE |
| BUILDING DEVOTED TO |
| THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED. |
| |
| PROVIDE THE SIZE OF EGRESS WIDTH AND THE OCCUPANCY LOAD |
| COUNT THROUGH THOSE EXITS. |
| |
| PLEASE REVIEW AND PROVIDE. |
| |
| |
| |
| 4) SHEET 3.0 - THERE IS NO INDICATIONS OF THE |
| SEPARATION OF THE REQUIRED EGRESSES. |
| |
| 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| EXIT DISCHARGE IS |
| REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| EXITS, EXIT ACCESSES, |
| OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| OTHER AND BE |
| ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| HAS THE |
| POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| EMERGENCY |
| CONDITION. |
| 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| DISCHARGES ARE |
| REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| ANOTHER NOT |
| LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| DIAGONAL |
| DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| MEASURED IN A |
| STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| EXIT ACCESSES, OR |
| EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| THROUGH |
| 7.5.1.3.5. |
| |
| PER # 1 ABOVE, PLEASE PROVIDE THE DIMENSION OF THE |
| SEPARATION OF EGRESS |
| |
| |
| |
| 5) SHEET 3.0 - THERE IS NO CLEAR EXIT SIGANGE WITH |
| ILLUMINATION. |
| |
| 7.10 MARKING OF MEANS OF EGRESS. |
| 7.10.1 GENERAL. |
| 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| MARKED IN |
| ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS |
| 11 |
| THROUGH 43. |
| 7.10.1.2 EXITS. |
| 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| THAT OBVIOUSLY |
| AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| BY AN APPROVED |
| SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| ACCESS. |
| 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH |
| WITHIN AN EXIT |
| ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR |
| DIRECTIONAL EXIT SIGNS |
| WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT |
| OBVIOUS. |
| |
| PLEASE REVIEW AND PROVIDE. |
| |
| |
| |
| 6) SHEET 3.0 - THERE IS NO INDICATION OF EGRESS |
| LIGHTING |
| |
| 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| 7.8.1 GENERAL. |
| 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| PROVIDED IN |
| ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND |
| STRUCTURE WHERE |
| REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF |
| THIS |
| REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| STAIRS, AISLES, |
| CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| TO AN EXIT. FOR THE |
| PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL |
| INCLUDE ONLY |
| DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| ESCALATORS, WALKWAYS, AND EXIT |
| PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| CONTINUOUS DURING THE |
| TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE |
| MEANS OF EGRESS |
| BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN |
| 7.8.1.2.2. |
| 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH |
| LOCATIONS AND FOR |
| SUCH PERIODS OF TIME AS ARE NECESSARY TO MAINTAIN THE |
| ILLUMINATION TO THE |
| MINIMUM CRITERIA VALUES HEREIN SPECIFIED. |
| |
| PLEASE REVIEW AND PROVIDE. |
| |
| |
| |
| 7) SHEET 3.0 - PER THE APPLICABLE OCCUPANCY CHAPTER |
| EMERGENCY LIGHTING IS NOT INDICATED. |
| |
| 7.9 EMERGENCY LIGHTING. |
| 7.9.1 GENERAL. |
| 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| EGRESS SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE |
| FOLLOWING: |
| (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| 11 THROUGH 43 |
| (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS |
| ADDRESSED IN SECTION |
| 11.7 |
| (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS |
| OF THIS CODE |
| (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS |
| (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF |
| ENCLOSURES, FOR WHICH THE |
| FOLLOWING ALSO APPLY: |
| (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO |
| INCLUDE A |
| STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF |
| ENCLOSURE MECHANICAL VENTILATION EQUIPMENT. |
| (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED |
| FOR THE |
| STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER |
| SUPPLY. |
| (6) NEW ACCESS-CONTROLLED EGRESS DOORS IN ACCORDANCE |
| WITH 7.2.1.6.2 |
| |
| PLEASE REVIEW AND PROVIDE. |
| |
| |
| 8) SHEET 3.2 & 10.1 - THE REAR DOOR IS NOT INDICATED ON |
| THE DOOR SCHEDULE, INCLUDING NO HARDWARE. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| IF THIS IS ALSO A REQUIRED EXIT DOOR, (WHICH IT |
| SHOULDBW) ALL EXIT HARDWARE SHALL BE INCLUDED. |
| |
| |
| |
| 9) PLEASE SECURE AND BIND ALL APPLICABLE SHEETS INTO 2 |
| COMPLETE SETS NOT 6 SEPARATE SHEETS. |
| |
| |
| |
| 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |