2020-04-24 09:27:02 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | 2ND BUILDING REVIEW DENIED: | | | | CORRECTIONS NEEDED ? FBC WPB AMENDMENTS 107 | | | | 1) FAILED: THE NEW DRAWING A?1 HAS A DETAIL FOR A | | LEDGER BOARD DETAIL | | SHOWING 3/8" TAPCONS AT 12" O.C. INTO A STEEL BEAM ? | | TAPCONS ARE NOT AN ACCEPTABLE ANCHOR FOR ATTACHMENT TO | | A STEEL | | BEAM, PLEASE REVISE DETAIL. PLEASE SHOW THE TYPE LENGTH | | AND DIAMETER OF THE ANCHOR TO BE USED. | | | | 2) OK | | | | 3) OK (PER PRODUCT APPROVA) | | | | 4) FAILED: PLEASE SHOW THE DETAILS FE EXTERIOR WALL | | INFILL. | | | | | | 5) OK |
|