Plan Review Notes For Permit 20021000 |
Permit Number |
20021000 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-02-28 15:28:17 | SFR REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) DRAWING A-1 HAS A DETAIL FOR A LEDGER BOARD DETAIL | | SHOWING 5/8" LAG BOLTS INTO A STEEL BEAM - LAG BOLTS | | ARE NOT AN ACCEPTABLE ANCHOR FOR ATTACHMENT TO A STEEL | | BEAM, PLEASE REVISE DETAIL. PLEASE SHOW THE TYPE LENGTH | | AND DIAMETER OF THE ANCHOR TO BE USED. | | 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED - FBC | | R301.2.1.1 - - - FBC 1603.1.4 | | 3) PLEASE SHOW THE EXTERIOR DOOR OPENING WIND DESIGN | | PRESSURE FBC R301.2.1 | | 4) PLEASE SHOW THE DETAILS FOR THE EXTERIOR WALL | | INFILL. | | 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVALS FOR THE NEW EXTERIOR DOOR. |
|