2020-04-10 13:19:582ND REVIEW FBC-2017 MECHANICAL
 PERMIT #20020949
 4/10/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CALCULATION SUMMARY SHOWS THE 8.5-TON CARRIER
 RTU IS OVER SIZED. THE CALCULATIONS INDICATE 74.1 MBH
 TOTAL COOLING AND 57 MBH SENSIBLE COOLING REQUIRED
 (APPROX. 6.5 TON), HOWEVER THE RTU-1 SCHEDULE ON THE
 PLAN INDICATES 103 MBH TOTAL AND 81 MBH COOLING-
 SECTION C403.2.1 FBC EC.
  
 2) COMMENT #4 FROM THE 1ST REVIEW HAS NOT BEEN
 ADDRESSED ON THE PLAN. 4) M2.1 & M6.1: INDICATE HOW O/A
 IS BEING PROVIDED TO THE LARGE CONFERENCE ROOM AND
 PROVIDE CALCULATIONS- TABLE 403.3.1.1 FBC M. PLEASE
 NOTE THAT AN AUTOMATICALLY CONTROLLED SHUTOFF DAMPER IS
 REQUIRED FOR THE REQUIRED O/A INLET OR DUCT TO THE AIR
 HANDLER- SECTION C403.2.4.3 FBC EC.
  
 3) THE REQUESTED ENGINEERING FOR INSTALLATION OF THE
 RTU HAS NOT BEEN PROVIDED. PLEASE NOTE THE ENGINEERING
 MAY BE DEFERRED- SECTION 107.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  