2020-02-26 06:29:41 | 1) EXISTING PLANS ON FILE WITH THE CITY SHOW THE |
| FOLLOWING APPLIANCES ON THE EXISTING GAS SYSTEM. THE |
| BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO |
| THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| THE TYPE OF THE EXISTING APPLIANCES, THE BTU LOAD OF |
| EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| WATER HEATER - 40,000 BTU'S |
| COOKTOP - 60,000 BTU'S |
| FUTURE BBQ - 45,000 BTU'S |
| DRYER - 22,000 BTU'S |
| 2) THE EXISTING GAS PLAN ON FILE WITH THE CITY SHOWS A |
| DEVELOPED LENGTH OF 116 FEET TO THE MOST REMOTE OUTLET |
| ON THE SYSTEM. THIS LENGTH SHALL BE USED FOR THIS |
| SYSTEM, NOT 32 FEET AS SHOWN ON THE SUBMITTED |
| RISER.2017 FBC-FUEL GAS SEC. 402.4.1. |
| 3) THE SUBMITTED GAS SIZING TABLE FOR THE PE PIPE IS |
| FROM THE 2006 EDITION OF NFPA 54. THE EDITION IN EFFECT |
| IS THE 2015 EDITION. SUBMIT A COPY OF THE SIZING TABLE |
| FROM THE CURRENTLY ADOPTED EDITION. NOTE: THE SIZING |
| TABLE NUMBER HAS CHANGED. IT IS NO LONGER TABLE 6.2 |
| (S). |
| 4) THE MINIMUM SIZE PE LINE TO THE GENERATOR SHALL BE 1 |
| 1/2 INCHES BASED ON THE 116 FEET DEVELOPED LENGTH AND |
| THE SIZING TABLE. |
| 5) THE CORRECT TOTAL BTU LOAD ON THE SYSTEM SHALL BE |
| LISTED ON THE GAS PLANS.WPB AMND. TO FBC SEC. 107.2.1, |
| 2017 FBC-FUEL GAS SECS.401.8, 402.2 |
| 6) SHOW THE SIZE AND THE TYPE OF PIPE COMING OFF THE |
| METER. THIS LINE SHALL BE SIZE FOR THE MAXIMUM DEMAND |
| ON THE SYSTEM. 2017 FBC-FUEL GAS SEC.402.1. |
| 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| GENERATOR.WPB AMEND. TO FBC SEC. 107.2.1. |
| 8) SUBMIT AN EXPANDED VIEW OF THE PIPING ARRANGEMENT AT |
| THE GAS METER.THE GAS RISER APPEARS TO SHOW TWO |
| SEPARATE LINES ON THE DISCHARGE SIDE OF THE |
| METER.CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |