2020-03-20 14:47:01FIRE ALARMS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - A CHANGE OF USE OF THE SINGLE
 FAMILY HOUSE TO AN R3 OCCUPANCY CLASSIFICATION NEEDS TO
 COMPLY WITH FBC EXISTING BUILDING CHAPTER 10 (CHANGE OF
 OCCUPANCY)
 1) PLEASE SHOW THAT THE SINGLE FAMILY HOUSE HAS
 EXISTING SPRINKLERS THAT COMPLY WITH FBC 310.5.1 CARE
 FACILITIES WITHIN A DWELLING.
 CARE FACILITIES FOR FIVE OR FEWER PERSONS RECEIVING
 CARE THAT ARE WITHIN A SINGLE-FAMILY DWELLING ARE
 PERMITTED TO COMPLY WITH THE FLORIDA BUILDING CODE,
 RESIDENTIAL PROVIDED AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.3 OR
 SECTION P2904 OF THE FLORIDA BUILDING CODE,
 RESIDENTIAL.
  
 FBC EXISTING BUILDING 1001.2 CERTIFICATE OF OCCUPANCY.
 A CHANGE OF OCCUPANCY OR A CHANGE OF OCCUPANCY WITHIN A
 SPACE WHERE THERE IS A DIFFERENT FIRE PROTECTION SYSTEM
 THRESHOLD REQUIREMENT IN CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING SHALL NOT BE MADE TO ANY
 STRUCTURE WITHOUT THE APPROVAL OF THE CODE OFFICIAL.
  
 2) A SEPARATE PERMIT IS REQUIRED FOR THE CHANGE OF
 OCCUPANCY.
  