2020-03-05 06:55:09 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE TWO COPIES OF PLANS, ONLY ONE PLAN |
| SUBMITTED. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED |
| AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED |
| BY THE ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT |
| ANY ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE |
| THAT ON PLAN. FS 471.003(2)(H); 471.025; WPB FBC |
| 107.2.1, 107.3.5 |
| |
| 2. VALUE LOW FOR AMOUNT OF WORK SHOWN, PROVIDE ACCURATE |
| VALUE OR VALUE WILL BE SET BY BUILDING OFFICIAL. |
| INFORMATIONAL NOTE. FIRE ALARM DESIGNS $5000 AND OVER |
| MUST BE DESIGNED AND SIGNED/SEALED BY A DESIGN |
| PROFESSIONAL. FBC 105.3.1.2 #4 |
| |
| 3. PASS FIRE REVIEW |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |