Date |
Text |
2020-06-16 12:34:02 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT-20020775 |
| 6/16/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P0.1 & P1.1: THE PLUMBING PLANS SHOW THE OIL |
| SEPARATORS DISCHARGING INTO A STORM DRAIN CATCH BASIN |
| WHICH IS PROHIBITED PER SEC. 90-203 (B) WPB CODE OF |
| ORDINANCE UNLESS THE FACILITY HAS A VALID NPDES PERMIT. |
| |
| 1A) THE PLUMBING CODE UNDER SECTION 1003.1 FBC P |
| REQUIRES THAT INTERCEPTORS AND SEPARATORS SHALL BE |
| PROVIDED TO PREVENT THE DISCHARGE OF OIL, GREASE, SAND |
| AND OTHER SUBSTANCES HARMFUL OR HAZARDOUS TO THE PUBLIC |
| SEWER, THE PRIVATE SEWAGE SYSTEM OR THE SEWAGE |
| TREATMENT PLANT OR PROCESSES.THE INTENT OF THE CODE IS |
| TO ENSURE PROPER REMOVAL OF HARMFUL SUBSTANCES FROM THE |
| WASTE WATER PRIOR TO DRAINAGE INTO A SANITARY SEWER |
| SYSTEM, BUT NOT A STORM DRAINAGE SYSTEM. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
| |
| |